KIP wire
For cubicles/distribution boards! This is a wire with a rich variety of compliance standards and applicable standards.
We would like to introduce our "KIP Electric Wire." The applicable standards for this product include JIS C 3005 (Test Methods for Rubber and Plastic Insulated Wires), as well as JIS C 3102 (Soft Copper Wire for Electrical Use) and JIS C 3152 (Tin-Plated Soft Copper Wire). It can be used for cubicles/distribution boards. 【Applicable Standards】 ■ JIS C 3005: Test Methods for Rubber and Plastic Insulated Wires ■ JIS C 3102: Soft Copper Wire for Electrical Use ■ JIS C 3152: Tin-Plated Soft Copper Wire ■ JIS C 3611: Insulated Wire for 6.6KV Receiving Cubicle Type Unit Substation *For more details, please refer to the related link page or feel free to contact us.
basic information
【Specifications (Excerpt)】 ■Number of conductors: 1 ■Conductor ・Nominal cross-sectional area (mm²): 250 ・Number of strands/strand diameter (No./mm): 61/2.3 ・Nominal outer diameter (mm): 20.7 ■Insulation thickness (mm): 4.5 ■Finished outer diameter ・Nominal (mm): 30.0 ・Permissible tolerance (+/-mm): 1.2 ■Conductor resistance (Ω/Km): 0.0744 ■Insulation resistance (MΩ·Km): 50 ■Test voltage (V/1min): 18,000 ■Standard length (m/drum): 150 ■Packaging method: Drum *For more details, please refer to the related link page or feel free to contact us.
Price range
Delivery Time
Applications/Examples of results
【Usage】 ■ For cubicles/distribution boards *For more details, please refer to the related link page or feel free to contact us.