MSA FL500-H2 Flame Detector
Quickly detect hydrogen fires. UV/IR flame detector with explosion-proof certification in Japan.
The FL500-H2 is a UV/IR flame detector specifically designed for hydrogen flames, provided by General Monitors. It uses a hybrid sensor that combines ultraviolet (UV) and infrared (IR) to sensitively detect the infrared and ultraviolet components emitted by hydrogen fires. It has obtained Japanese explosion-proof certification, making it ideal for use in environments with a risk of hydrogen leaks, such as hydrogen stations and storage facilities. It features a robust stainless steel housing and continuous optical self-checking (COPM), ensuring excellent reliability and maintainability.
basic information
Detection Method: UV/IR combined detection (UV: 185–260nm / IR: 435µm) Field of View: Cone-shaped field of view with a maximum of 130° Detection Target: Hydrogen flame Response Time: Less than 3 seconds at a distance of 60ft Self-Diagnosis: Automatically performed every 2 minutes (COPM) Output: 0–20mA analog output Power Supply: 20–36VDC, maximum 200mA/3W Housing Material: 316 stainless steel (powder coated) Protection Rating: IP66/IP67 Operating Temperature: -55 to +85° Certification: ATEX, IECEx, FM, CSA, CE, etc. Size & Weight: Φ114×L140mm / 4.0kg
Price range
Delivery Time
Model number/Brand name
MSA
Applications/Examples of results
Hydrogen stations and filling stations, hydrogen storage and supply equipment, electrolysis devices and renewable energy-related equipment, experimental facilities and research institutes using hydrogen, etc.