4KGM Freezer Machine [Manufactured by Sumitomo Heavy Industries] [Authorized Dealer]
The 4K-GM ultra-low temperature refrigeration system at Sumitomo Heavy Industries is highly reliable and orientation-free, making it suitable for a wide range of applications.
It is used for reducing helium evaporation (such as in MRI), cooling superconducting magnets, and cooling sensors. With the price of liquid helium skyrocketing and its availability becoming extremely difficult, it is recommended as an alternative to liquid helium. ● You can download the "comprehensive catalog" that includes this product. Please feel free to contact us if you have any questions.
basic information
You can download the "comprehensive catalog" that includes this product. If you have any questions, please feel free to contact us.
Price range
Delivery Time
Applications/Examples of results
For more details, please contact us.
Line up(7)
Model number | overview |
---|---|
RDK-101D(L) | 〇Freezing capacity (50/60Hz) 1st (60K): 3.0/5.0W 2nd (4.2K): 0.1/0.1W 〇Minimum reaching temperature: 3.0K (RDK-101D)/<2.3K (RDK-101DL) 〇Cooldown time: (<150 minutes from 300K to 4.2K) 〇Weight: 7.2kg 〇Dimensions: (H×W×D) 442×130×226mm 〇Recommended maintenance cycle: 10,000 hours 〇Safety standards UL/CE, RoHS |
RDK-305D2 | 〇 Freezing capacity (50/60Hz) 1st (40K): 15/20W 2nd (4.2K): 0.4/0.4W 〇 Minimum reachable temperature: <3.5K 〇 Cool down time: (from 300K to 4.2K) <120 minutes 〇 Weight: 16.0kg 〇 Dimensions: (H×W×D) 512×180×294mm 〇 Recommended maintenance cycle: 10,000 hours 〇 Safety standards UL/CE, RoHS |
RDK-205D2 | 〇 Freezing capacity (50/60Hz) 1st (50K): 10/13W 2nd (4.2K): 0.5/0.5W 〇 Minimum achievable temperature: <3.5K 〇 Cool down time: (from 300K to 4.2K) <90 minutes 〇 Weight: 14.0kg 〇 Dimensions: (H×W×D) 512×180×294mm 〇 Recommended maintenance cycle: 10,000 hours 〇 Safety standards UL/CE, RoHS |
RDK-408D2 | 〇 Freezing capacity (50/60Hz) 1st (43K): 40/50W 2nd (4.2K): 1.0/1.0W 〇 Minimum achievable temperature: <3.5K 〇 Cool down time: (from 300K to 4.2K) <60 minutes 〇 Weight: 18.0kg 〇 Dimensions: (H×W×D) 557×180×294mm 〇 Recommended maintenance cycle: 10,000 hours 〇 Safety standards UL/CE, RoHS |
RDE-412D4 | 412D4 〇Freezing capacity (50/60Hz) 1st (43K): 53/60W 2nd (4.2K): 1.25/1.25W 〇Minimum achievable temperature: <3.5K 〇Cooldown time: (from 300K to 4.2K) <60 minutes 〇Weight: 22.0kg 〇Dimensions: (H×W×D) 554×180×306mm 〇Recommended maintenance cycle: 10,000 hours 〇Safety standards UL/CE, RoHS |
RDK-415D2 | 〇 Freezing capacity (50/60Hz) 1st (50K): 50/50W 2nd (4.2K): 1.5/1.5W 〇 Minimum achievable temperature: <3.5K 〇 Cool down time: (from 300K to 4.2K) <60 minutes 〇 Weight: 18.5kg 〇 Dimensions: (H×W×D) 557×180×294mm 〇 Recommended maintenance cycle: 10,000 hours 〇 Safety standards UL/CE, RoHS |
RDE-418D4 | 〇 Freezing capacity (50/60Hz) 1st (42K): 50/50W 2nd (4.2K): 1.8/2.0W 〇 Minimum achievable temperature: <3.5K 〇 Cool down time: (from 300K to 4.2K) <60 minutes 〇 Weight: 20.0kg 〇 Dimensions: (H×W×D) 554×180×306mm 〇 Recommended maintenance cycle: 10,000 hours 〇 Safety standards UL/CE, RoHS |
catalog(1)
Download All CatalogsRecommended products
Distributors
Our company entered the cryogenic business in 1970. In 1993, we fully entered the low-temperature physical property measurement equipment market, focusing on quickly, affordably, and user-friendly supplying products tailored to our customers' needs in partnership with distinctive domestic and international manufacturers. Based on our flagship measurement system, the Cryo refrigeration unit, we have a proven track record of assisting in numerous developments in the energy and power sector, industrial and transportation sector, and analysis and information sector, primarily utilizing superconducting technology.